KUBAIR® F400 CC / MV

F400 120 extraction boxes

Direct drive - reaction < 23000 m3/h

KUBAIR F400 MV View larger

KUBAIR® F400 CC / MV

F400 120 extraction boxes


Direct drive - reaction < 23000 m3/h

Conforme ErP 2018 ErP - UVNR Compliant ErP 2018 - UVNR
Agréé 400°C 2h Conformité Européenne Isolation acoustique
Maintenance facilitée Coffret relayage Monté/Câblé OPTAIR® Ventilation, EASYVENT, OPTAIR® VVTP

  • High performance jet turbine
  • F400 120 approved with relay box
  • Multidirectional connection
  • Easy maintenance and cleaning
  • Waterproof kitchen version
  • KUBZ 10 manual flow adjustment device

Application

Extraction of fumes and hot gases in case of fire.
Extraction of stale air from tertiary and industrial premises.
Extraction of pollutants in professional kitchens.
Maximum temperature of the air extracted in steady state: 120°C.
Installation in all positions and connection on all sides, except with vertical motor axis and motor at the bottom.


  • Description

  • Dimensions

  • Documentation

  • Public Price

  • Software

  • References

Flows from 500 to 23,000 m3/h.
8 sizes: 355 / 400 / 450 / 500 / 560 / 630 / 710 / 800.
KUBAIR F400 CC: complete unit with multidirectional suction plenum, horizontal or vertical axis motor.
KUBAIR F400 MV: ventilation unit only, horizontal or vertical axis motor.

Options - Corrosion treatment


KUBAIR F400 - Main spare parts


Construction
  • Interchangeable galvanized sheet steel panels.
  • Modular structure in aluminum profiles.
  • 4 fixing brackets.
  • Connection by 2 smooth flanges KUBZ12 included, interchangeable.
  • Galvanized steel reaction turbine, mounted in direct coupling with the motor.
  • Access to the interior for cleaning and maintenance without uncoupling the casing.

Motorization
  • AC B5 motor, IP 55 class F.
  • Optional PTO thermal protection.
  • Single-phase 230V 50Hz 1 speed 2, 4 or 6 poles, IE1 or IE3 accepts voltage variation.
  • Three-phase 230/400V 50Hz 1 speed 2, 4, 6 or 8 poles, IE2 or IE3, accepts frequency variation.
  • Three-phase 400V 50Hz 2 speeds, 4/6, 4/8, 6/8 or 6/12 poles, Dahlander or independent windings.

Factory fitted and approved electrical equipment F400 120
  • INTZ: padlockable proximity switch with 2 auxiliary contacts (1 NO and 1 NC).
  • BDEZ: 20-300 Pa pressure switch fitted, not connected to the aeraulics, to be adjusted on site.
  • PILOTAIR® : relay box
    • For certain ratings, the box can be supplied mounted wired on the motor cover, protected by a visor
    • For all ratings, it can be supplied as an accessory or simply wired.

F400 120 Approved Installation Accessories
  • KUBZ 14 - Kitchen option
    • Reinforced sealing with grease resistant seal.
    • Drain purge supplied not fitted.
    • Uninsulated double skin.
  • KUBZ 09 - Double skin insulated 25 mm rock wool M0.
  • KUBZ 10 - Manual flow control damper
    • Positions itself at the repression. Allows to reduce the flow (between 5% and 30%) and adjust the operating point.
  • KUBZ 16 - Pressure damper to be mounted on the discharge
    • Ensures a good water and air tightness when the casing is stopped.
    • Accessory for horizontal shaft motor box.
  • KUBZ 17 - Pressure damper to be mounted on the discharge
    • Ensures a good water and air tightness when the casing is stopped.
    • Accessory for vertical shaft motor box. F400 120 approved.

Selection of smoke extraction fans
MV version
Assembly with horizontal motor axis
KUBAIR-F400-MV-H-dim

MV version
Assembly with vertical motor shaft
KUBAIR-F400-MV-V-dim.png

CC version
Assembly with horizontal motor axis
KUBAIR-F400-ECOWATT-CC-H-dim

CC version
Assembly with vertical motor shaft
KUBAIR-F400-CC-V-dim

Size

A

BH

BV

BVC

C

D

E

EC

355

627

695

327

645

263

559

606

790

400

699

767

361

678

297

631

606

864

450

779

847

392

738

326

711

606

990

500

858

925

424

784

338

768

700

1039

560

954

1021

441

817

354

864

700

1139

630

1066

1133

488

912

403

977

700

1183

710

1194

1261

551

1032

462

1104

906

1325

800

1338

1420

574

1084

488

1248

906

1379


Size

F

G

GC

H

J

K

KC

L

355

660

31

50

315

102

677

954

321

400

732

31

50

349

102

711

1022

321

450

812

31

50

378

102

743

1081

321

500

890

42

62

402

112

805

1145

351

560

986

42

62

419

112

822

1178

351

630

1098

42

62

466

112

869

1273

351

710

1226

42

62

526

112

994

1488

446

800

1370

42

62

552

127

1050

1540

446

Close Open Detailed specifications

Close Open Public tariff price

Price catalog pages (CP)

Close Open Fire / Smoke extraction certificates

Close Open Electrical / ATEX Certificates

Electrical CE Declarations (DCCE)

OPTAIR Ventilation
Download OPTAIR Ventilation Media locked
Selection software for turrets and extraction boxes / introduction: KDT / KSH / TCD / KUBAIR / TED
For any operating problem, please send your request by email to optair@vim.fr

  • Creation of a technical sheet per fan including the operating point requested on the curve, the technical and acoustic characteristics, and the dimension drawings
  • Printing possibility
  • Link to all technical pages Catalog
January 2024 - New version OPTAIR Ventilation 2024.1.2.0
  • Integration of the tariff on 01/02/2024
  • Obsolete engine removals
  • Miscellaneous Corrections

OPTAIR VVTP
Download OPTAIR VVTP Media locked
Software for calculating the ventilation rate in a technical room (VTP) housing a smoke extraction fan

OPTAIR-CTA-1-400px.jpg         
  • Calculation according to the smoke extraction flow rate, the installed extractor, the ductwork and the characteristics of the room.
  • Facilitates the optimisation of flow rates by adjusting the various parameters
  • Selection of air supply grilles or dampers.
  • Summary technical data sheets.
X