CAD HR FIRST V

Old ranges

Counter flow - Forward < 3500 m3/h

FLAG Obsolete
CAD HR FIRST V View larger

CAD HR FIRST V

Old ranges


Counter flow - Forward < 3500 m3/h

erp.jpg ErP 2018 compliant - UVNR
3 or 4 speed AC motors
Filters
Supplied as standard: Blowing fresh air F7 (ePM1 70%). Reprise stale air M5 (ePM10 50%).
by-pass.jpg echangeur.jpg modbus.jpg
chaud-froid.jpg plug-and-play.jpg Loogiciel.jpg
Logo-EUROVENT.jpg
Air-to-air plate heat exchanger produced by the RECUTECH company which participates in the Eurovent program. Certification for AAHE.





  • Economic range
  • Double skin insulation 25 mm
  • With or without integrated battery
  • Modbus communicating EVOD regulation
  • Thermal efficiency up to 85%

Application

Air introduction and extraction with heat recovery.
Installation on feet.
Indoor or outdoor use with rainscreen.
Heating of the blown air by electric coil or hot water depending on the model.

  • Description

  • Dimensions

  • Documentation

  • Public Price

  • Software

  • References

5 sizes: 04 (400m3/ h) / 07 (700m3/ h) / 18 (1,800m3/ h) / 26 (2,600m3/ h) / 33 (3,300m3/ h).
6 models according to the types of integrated batteries:

Post-heating electric Post-heating hot water Electric antifreeze
D
DD
DI
DDI
DC
DDC

Vertical construction (V) control cabinet on the left in the direction of the fresh air (G).
Connection of the ducts in line with the position of certain connections configurable on site.
EVO regulation with remote control.
EVOD regulation with remote control, communicating Modbus: connection on the regulation card in RS485 or TCP / IP to the BMS.
Webserver application on TCP / IP port.
Multi-speed operation by remote control or external 0-10V signal.
By-pass 100%.

Construction
  • Self-supporting structure in extruded aluminum profile.
  • Aluminum zinc panel, 25 mm double skin, insulation by injected polyurethane foam (42 kg / m3-0.0246W / m, k) fire classification B-S3, d0 (M1).
  • Black painted galvanized steel support feet.
  • Vertical construction with in-line connection by circular taps fitted with a seal. Possibility of adapting certain taps on site.
  • Access to filters, exchanger, coil, and fan from the side.
  • Ø1 / 2 '' drain for condensate evacuation.

Exchanger
  • Aluminum plate heat exchanger, counter current, high efficiency, low pressure drop.

Motorized bypass
  • Delivered assembled, installed on the fresh air network.
  • By-pass 100% with shutter for closing the air passage on the exchanger when the bypass is open, to take full advantage of free cooling.
  • 230V single-phase, all-or-nothing servo-motor.

Motorization
  • Double inlet fans, forward turbine, built-in motor, mounted IP 55 electrical box.
  • AC motor with integrated thermal protection:
    • CAD HR FIRST 04/07: 4 speeds, single phase 230V, 50Hz, IP 20 class F
    • CAD HR FIRST : 3 speeds, single phase 230V, 50Hz, IP 20 class F
    • CAD HR FIRST 33: 3 speeds, single phase 230V, 50Hz, IP 20 class B

Filters
  • M5 (ePM10 50%) during extraction.
  • F7 (ePM1 70%) on the introduction of fresh air.

DI post heating electric coil
  • Connected to the regulation, it allows the temperature of the blown air to be regulated.
  • Equipped with safety thermostat with automatic reset (set point 50 ° C) and manual reset (set point 65 ° C).

DC hot water coil
  • 2-row coil, made up of copper tubes with aluminum fins on a galvanized steel frame, copper manifold, threaded connection tube.

DD antifreeze electric heater
  • Placed on the fresh air before the exchanger, avoids the risk of freezing on the exchanger.
  • Raised, wired and controlled by the regulation.
  • Separate power supply, connection to a specific external box fitted with a proximity switch.
  • Safety thermostat with automatic reset (set point 50 ° C) and manual reset (set point 65 ° C).

Air treatment selection
CADHR-FIRST-V-dim.png


Outdoor air
Extract air
Supply air
Exhaust air


Cut

A

B

C

D

E

F

G

H

I

K

L

ØP

ØQ

ØR

S

T

U

V

Weight

(kg) *

04

450

1420

900

225

232

520

550

150

150

808.5

611

200

1/2 ''

1/2 ''

60

41

174

100

98.5

07

550

1420

900

275

232

520

550

170

170

808.5

611

250

1/2 ''

1/2 ''

60

41

174

100

115

18

840

1800

1110

420

285

625

655

255

255

1010

790

315

1/2 ''

1/2 ''

60

41

174

100

276

26/33

1050

2180

1340

525

342

735

775

219

319

1175

1005

400

1/2 ''

3/4 ''

60

41

174

100

363/379

* Unit weight without right and / or left battery

Vertical roofs


Cut

F

G

H

Weight

(kg)

04

1620

770

165

19

07

1620

870

165

21

18

2000

1160

165

33

26/33

2380

1370

175

45

Close Open Detailed specifications

Text catalog pages (CT)

Close Open Installation instructions

Installation / maintenance manual (NT)

X