CHGT F400 - CHGT F200

Axial fans F400 or F200

In boxes

CHGT F400 - CHGT F200 View larger

CHGT F400 - CHGT F200

Axial fans F400 or F200


In boxes

ErP.jpg ErP 2015 compliant
Fan
CE.jpg PIC-logiciels.jpg

  • Axial box fan
  • Box with sound insulation
  • Wide flow / pressure range


Application

Extraction of fumes and hot gases in case of fire.
Extraction of stale air from tertiary and industrial premises.
Air extraction and smoke extraction from covered parking lots.
Indoor or outdoor installation for horizontal air flow.

  • Description

  • Dimensions

  • Documentation

  • Public Price

  • Software

  • References

  • Flow rates from 600 to 130,000 m3/ h.
  • 2 models: approved F400 120 or approved F200 120.
  • 10 sizes: Ø 400/450/500/560/630/710/800/900/1000/1250.

Construction
  • Galvanized steel box with soundproofing in 25 mm M0 fiberglass.
  • Ferrule and motor support in thick hot-dip galvanized sheet steel.
  • Square flange at suction and discharge.
  • High efficiency propeller, in injected aluminum, dynamically balanced according to ISO 1940. 3, 5, 6, 7 or 9 blades with variable tilt angles when stationary, to meet all flow / pressure requirements with precision. Direction of engine air - propeller (direction A).

Motorization
  • Three-phase AC asynchronous motor in direct coupling with the propeller.
  • Foot-mounted motor B3, IP55, class H. Services S1 and S2. Control possible by frequency variation.
  • Motor without thermal protection:
    • 1 three-phase speed 230 / 400V 50Hz 4 or 6 poles up to 3kW.
    • 1 three-phase speed 400V 50Hz 4 or 6 poles above 3kW.
    • 2 three-phase speeds 400V 50Hz 4/8, 4/6 or 6/12 poles Dahlander windings.

Selection of smoke extraction fans
CHGT 400 to 800


Model

A

B

C

D

E

F

400

509

423

440

40

520

304

450

567.6

473

783

40

563

317

500

638

523

525

40

605

331

560

718.6

583

570

40

650

370

630

808

653

570

40

650

370

710

907.6

750

640

40

720

438

800

1,007.6

850

640

40

720

438



CHGT 900 to 1250



Model

A

B

C

D

E

F

G

H

900

1,126.5

950

700

50

800

503

860

1,076.5

1000

1265.5

1,055

700

50

800

503

860

1,206.5

1,250

1476.5

1275

900

50

1000

310

1,060

1426.5

Close Open Installation instructions

Installation instructions (NT)

Close Open Performance / Environment Certificates

Close Open Commercial documents

Commercial leaflet (FCOM)

OPTAIR VVTP
Download OPTAIR VVTP Media locked
Software for calculating the ventilation rate in a technical room (VTP) housing a smoke extraction fan

OPTAIR-CTA-1-400px.jpg         
  • Calculation according to the smoke extraction flow rate, the installed extractor, the ductwork and the characteristics of the room.
  • Facilitates the optimisation of flow rates by adjusting the various parameters
  • Selection of air supply grilles or dampers.
  • Summary technical data sheets.
PARKING ECO QUARTIER - STRASBOURG

Close Open PARKING ECO QUARTIER - STRASBOURG

Tertiary car parks

67 - Bas-Rhin


Installed products:


PORTE ROMAINE - NIMES

Close Open PORTE ROMAINE - NIMES

Private collective housing

30 - Gard

THE CLOUD CITY

Close Open THE CLOUD CITY

Housing complex

59 - North


Installed products:


X