TCBB - TCBT

Axial fans

Tubular < 43,000 m3/h

TCBB-TCBT View larger

TCBB - TCBT

Axial fans


Tubular < 43,000 m3/h

PIC-Conforme-Erp.jpg ErP 2015 compliant
Fan
PIC-logiciels.jpg

  • standard version
  • Small footprint

Application

Extraction or introduction of air.
Introduction of fresh air into smoke extraction installations.
Air flow temperature from -40°C to +70°C depending on engine.
Horizontal or vertical installation.

  • Description

  • Dimensions

  • Documentation

  • Public Price

  • Software

  • References

10 sizes: 250 / 315 / 355 / 400 / 450 / 500 / 560 / 630 / 710 / 800.
Speeds from 250 to 43,200 m3/h.
2 power supplies:
  • TCBB: Single phase.
  • TCBT: Three-phase.

Construction
  • Aluminum propeller, fixed blades sizes 250 to 400, variables when stationary from 450 to 800, dynamically balanced following ISO 1940.
  • Air direction B as standard: propeller > motor.
  • Casing and flanges in galvanized steel protected from corrosion by cataphoresis and black polyester paint RAL 9011, stainless steel screws.
  • Terminal box with PG-11 cable gland fixed outside the shell for sizes 250 to 630, on the motor for sizes 710 to 800, standard cable.

Motorization
  • 1-speed class F 2, 4 or 6 pole single or three-phase AC motors and 2-speed 4/8 pole 3-phase 400V for sizes 450 to 800.
  • Mono motors with capacitor mounted in the terminal box.

Selection of technical fans
TCBB-TCBT 250 to 400

TCBB-TCBT 450 to 630 and 710 / 6 poles

Sizes

ØA

B

C

ØD

ØE

Number of holes

250

327

292

170

254

10

4

315

386

355

170

315

10

8

355

426

395

170

355

10

8

400 (4 poles)

487

450

210

400

12

8

400 (6 poles)

487

450

170

400

12

8

450

537

500

180

450

12

8

500

595

560

180

500

12

12

560

655

620

240

560

12

12

630

725

690

240

630

12

12

710 (6 poles)

806

770

240

710

12

16


TCBB-TCBT 710 / 4 poles and 800
TCBB-TCBT-7104p-800-dim.png

Sizes

ØA

B

C

ØD

E

4 Poles

6 Poles

8 Poles

710/L (4 poles)

806

770

380

710

415

710/H (4 poles)

806

770

380

710

444

800/L

896

860

380

800

437

408

383

800/K

896

860

380

800

448

437

408

800/G

896

860

380

800

447 (5.5kW)

515 (7.5kW)

448

437

800/H

896

860

380

800

515

477

437

Close Open Detailed specifications

Text catalog pages (CT)

Close Open Public tariff price

Price catalog pages (CP)

Close Open Installation instructions

Installation / maintenance manual (NT)

Close Open Electrical / ATEX Certificates

Electrical CE Declarations (DCCE)

Close Open Prescription assistance

Specification text (TP)

EASYVENT
Access the software online Media locked
Axial selection software and S&P group products

  • Creation of a technical sheet per fan including the operating point requested on the curve, the technical and acoustic characteristics, and the dimension drawings
  • Printing possibility
  • Link to all technical catalog pages

Close Open CENTRE HOSPITALIER - PLERIN

Hospitals

22 - Côtes-d'Armor

Close Open LECLERC GRAND AJACCIO BALEONE

Shopping centers

2A - Corse-Du-Sud

Close Open PETITES SOEURS DES PAUVRES

Residences for the elderly

39 - Jura


Installed products:


X