UTBS ECOWATT UP

Old ranges

H14 filtration

FLAG Obsolete
UTBS ECOWATT UP View larger

UTBS ECOWATT UP

Old ranges


H14 filtration

Size the purifier
PIC-FILTRES.jpg
Débit réguléGTC Modbus BACnetRégulation Plug & Play
Filters
Prefiltration G4 / Coarse 90% according to ISO 16890.
Fine filtration F7 / ePM1 70% according to ISO 16890.
Absolute filtration H14 Efficiency of 99.995 %
according to standard EN 1822-1.

  • Air purification by filtration
  • HEPA H14 filter according to standard EN 1822
  • Improvement of IAQ - Reduction of viruses
  • Constant flow, control of filter clogging
  • Small footprint height 360 to 500 mm
  • No clutter of floor space


Application

Indoor installation.
Installation in false ceiling, vertically in cupboard / wall or visible suspended, with or without air distribution network.
Offices, shops, education, sanitary facilities, leisure, accommodation, catering ...
Filtration of dust, fine particles, VOCs, pollens, spores, bacteria, viruses including SARS-CoV-2.
Recycling operation, no action on the CO2 rate or on the relative humidity.
Complementary device to a ventilation system with fresh air supply.
For rooms from 30 to 580 m² on the basis of a renewal of 3 volumes / hour (minimum flow rates recommended for rooms not classified ISO).
For large spaces, plan several units.
Constant flow rate operation, adaptation of the flow rate according to the clogging of the filters (2 adjustable flow rates).

  • Description

  • Dimensions

  • Documentation

  • Public Price

  • Software

  • References

Flow rates from 200 to 5200 m3 / h - 4 sizes.
  • Size 2: H = 360 mm, flow rate from 200 to 1200 m3 / h.
  • Size 3: H = 410 mm, flow rate from 500 to 2300 m3 / h.
  • Size 5: H = 410 mm, flow rate from 1000 to 3600 m3 / h.
  • Size 8: H = 500 mm, flow rate from 1000 to 5200 m3 / h.
Left L or right R easement in the direction of the air.
G4 Filter + Fan + F7 / H14 modules delivered assembled.
Silent module SIL - L = 750 mm.
Suction and blowing plenums with or without grid.
Unit delivered with wired mounted control and touch control.


Construction
  • Frame in extruded aluminum profiles.
  • Kit for fixing the modules together.
  • Double skin panels in galvanized steel coated with RAL 9010 exterior.
  • Acoustic insulation by A1 glass wool thick. 25 mm, density 24 kg / m3.
  • Hinged doors for easy access to the control unit.

Motorization
  • High performance freewheeling jet fans.
  • Electronically protected single-phase or three-phase (size 8) direct-coupled ECM motors.

Regulation
  • CAV mode - constant flow
  • Modbus communicating regulation on RS 485 port or BACnet IP on TCP / IP port.
  • Automatic operation in constant flow CAV to be adjusted on site
  • Control of filter clogging.
  • ETD remote touch screen equipped with a 10 m cable, extendable up to 50 m.
Horizontal installation - Left easement L
UTBS-ECOWATT-UP-L-dim.jpg
SizesABCDEFKLMN
28223601514689299750205485182505
31172410151410393491100205485182505
51572410151414393491500205485182505
81972500151418394391900205485182505



Vertical installation - Right easement R
UTBS-ECOWATT-UP-L-dim.jpg
SizesABCDEFGHJKLMN
282236018746892997503601514398205485182505
311724101924103934911004101514448205485182505
515724101924143934915004101514448205485182505
819725002014183943919005001514538205485182505



Vertical installation - Right easement R
UTBS-ECOWATT-UP-L-dim.jpg
SizesABCDEFGHJKLMN
282236015146892997503601521398205485182505
311724101514103934911004101521448205485182505
515724101514143934915004101521448205485182505
819725001514183943919004101521538205485182505

Close Open Installation instructions

Installation instructions (NT)

Installation instructions (NT) Other languages