KSEF ECOWATT

Simple flow AHU

Modular - Reaction - ECM < 12 000 m3/h

KSEF ECOWATT

Simple flow AHU


Modular - Reaction - ECM < 12 000 m3/h

Conformes ErP - UVNR - Moteur EC variableErP 2018 compliant
UVNR - Variable EC Motor
Moteur ECMDébit ou pression régulésGTC ModbusOPTAIR® CTA VIM

  • Low consumption ECM motor
  • 25 mm double skin insulation
  • Optional M5, F7 or F9 filtration
  • Reaction freewheel fan
  • Modular design

Application

Introduction of fresh air, filtration, heating and cooling.
Indoor or outdoor installation.
Treated air temperature -25 to +40°C.

  • Description

  • Dimensions

  • Documentation

  • Public Price

  • Software

  • References

Flow rates from 500 m3/h to 12,000 m3/h.
6 sizes: 18 / 40 / 55 / 75 / 95 / 120.

Regulations and management
  • Regulation by CORRIGO integrated automaton specific to VIM .
  • 3 operating modes: variable flow (VAV), constant flow (CAV), constant pressure (COP).
  • Communicating Modbus RTU on RS485 port or Modbus TCP/IP, BACnet IP or MSTP.
  • ETD2 remote touch control.

Configurations

  • Interiors without roof: D right easement - G left easement.
  • Exterior with roof mounted: EXD right easement - EXG left easement.
  • Add-ons
  • KB air treatment modules:
    • KBEI electric battery module
    • KBEC hot water battery module
    • KBER reversible water battery module
  • KPCA 3-stage filtration module: Metallic / M5 + F7 / F9 + Activated carbon cartridges.
  • KSIL silent module.
  • KFIL 2-stage filtration module.
  • KATH decontamination module: elimination of viruses and pollutants by athermal catalysis.

Construction
  • Modular structure in aluminum profile.
  • In-line construction, rectangular or circular connection.
  • Double skin panels equipped with peripheral seal.
  • Exterior in pre-painted galvanized steel, dark gray color RAL7024, corrosion resistance C5, ultraviolet resistance RUV5 according to EN 10169. Interior in galvanized steel Z275.
  • Insulation with glass wool, thickness 25 mm, density 24 kg/m3.
    • Thermal conductivity 0.035 W/(mk) (20°C).
    • Fire classification A1 according to standard EN 13 501.1.
  • Metallic freewheel type reaction fan (incombustible A1). ECM Mono 230V or Tri 400V motor depending on the size.
  • Switch mounted/wired.
  • Module delivered on feet (18 to 75) or chassis (95 to 120).

2-stage filtration
  • Metal pre-filter: FIME thickness 48 mm.
  • Pleated pre-filter: FIFI M5 ePM10 50% thickness 48 mm.
  • HPE FIFI F7 ePM1 55 Mini-Pleat Filters% or FIFI F9 ePM1 80% thickness 98 mm.

Registers (accessory)
  • Manual or motorized control.
  • Antifreeze protection for water batteries, mounted on the suction side.
  • Network closure in application of article CH38, mounted on blowing.

KB Battery Modules
KBEI - Electric battery module
  • 304L stainless steel resistors.
  • Safety thermostats: one thermostat with automatic reset at 85°C, one thermostat with manual reset at 120°C.
  • Anti-radiation screen, air inlet side.
  • Pulse train control.
  • Post-ventilation.
  • Separate 400V three-phase power supply with proximity switch.
KBEC - Hot water battery module
  • 2 or 4 row battery, with copper tubes, aluminum fins on a galvanized steel frame; threaded connection tubes.
  • Right or left connection in the direction of air flow.
  • Frost protection by contact probe.
  • Battery(ies) mounted on slide accessible via side hatch.
KBER - Cold or reversible water battery module
  • ER cold or hot water batteries.
  • 4-row battery, with copper tubes, aluminum fins on a galvanized steel frame; threaded connection tubes.
  • Right or left connection in the direction of air flow.
  • Change-over thermostat.
  • Frost protection by contact probe.
  • Battery(ies) mounted on slide accessible via side hatch.
  • Stainless steel condensate tray and droplet separator.

Silent module
KSIL - Acoustic baffle module
  • Baffles thickness 200 mm.
  • Rock wool 50kg/m3 protected by an anti-fiberglass veil.
  • Fire classification A1.
  • Kitchen option:
    • M0 (A1) expanded metal protection to facilitate cleaning and maintain acoustic performance.

Filtration module
KFIL - 2-stage filtration module
  • Metal pre-filter: FIME thickness 48 mm.
  • Pleated pre-filter: FIFI M5 ePM10 50% thickness 48 mm.
  • HPE FIFI F7 ePM1 55 Mini-Pleat Filters% or FIFI F9 ePM1 80% thickness 98 mm.


Air treatment selection
KSEF ECOWATT 18 / 40 / 55 / 75
Interior model without roof

KSEF-ECOWATT-18-75-interieur.jpg


Exterior model with roof

KSEF-ECOWATT-18-75-exterieur.jpg


SizeHASBCDEFGIMNOPWeight (kg)
Without roofWith roof
KSEF ECOWATT 18985644584538700100336076079857847966373
KSEF ECOWATT 40113569563563579510033757757113583589188120
KSEF ECOWATT 5512109819216357951003383283212101121891130161
KSEF ECOWATT 751270981921921108110033892892127011211177141156



KSEF ECOWATT 95 / 120 / 200
Interior model without roof

KSEF-ECOWATT-95-200-interieur.jpg


Exterior model with roof

KSEF-ECOWATT-95-200-exterieur.jpg


SizeHASBCDEFGNOPWeight (kg)
Without roofWith roof
KSEF ECOWATT 95147813061226967120215533147814461308230255
KSEF ECOWATT 1201959130612261272150715533195914461613353385


Close Open Detailed specifications

Catalog Pages - Other

Close Open Installation instructions

Close Open Fire / Smoke extraction certificates

Fire classification report (PVFEU)

Close Open Performance / Environment Certificates

Declaration of performance (DOP)

Close Open Electrical / ATEX Certificates

Electrical CE Declarations (DCCE)

Close Open Prescription assistance

X