KSDE ECOWATT®

Simple flow AHU

Compact - Reaction - ECM < 24,000 M3/h

Flag Nouveau
KSDE ECOWATT® View larger

KSDE ECOWATT®

Simple flow AHU


Compact - Reaction - ECM < 24,000 M3/h

Conforme ErP 2018 - UVNRCompliant ErP 2018 - UVNR
Filters
Delivered as standard: FIFI M5 ePM10 75 mini pleat filters%.
Additional filters available as an option: FIFI F7 ePM1 55% HPE (High Energy Performance) minifolds / FIFI F9 ePM1 80% HPE miniplies.
Additional options in sizes 160 and 200: FIFI F7 ePM1 60% with soft pockets / FIFI F7 ePM1 55% with rigid pockets / FIFI F9 ePM1 85% with soft pockets / FIFI F9 ePM1 80% with rigid pockets.
Moteur ECMDébit ou pression régulésGTC Modbus et BACnet
Régulation Plug and PlayOPTAIR CTA

  • Communicating Modbus and BACnet control
  • High level of finish and performance
  • Free-wheeling fan with reaction
  • Double skin rock wool insulation 50 mm
  • Low consumption ECM motor

Application

Introduction of fresh air, heating and/or cooling.
Indoor or outdoor installation.
Treated air temperature -25 to +40°C.

  • Description

  • Dimensions

  • Documentation

  • Public Price

  • Software

  • References

Flow rates from 2,000 to 24,000 m3/h.
5 single-block sizes 40 / 55 / 75 / 95 / 120 and 2 double-block sizes 160 and 200.
9 models according to the types of integrated batteries:

ElectricHot waterCold waterReversible waterDirect relaxation
EI
EIX
EIF
EC
ER
ECF
EX
ERC
ERR x2


Configurations:
  • Exterior with roof mounted:
    • EXD : easement on the right,
    • EXG : easement on the left.
  • Interior without roof:
    • D: easement on the right,
    • G: easement on the left.

Regulation:
  • VIM specific integrated CORRIGO automaton.
  • 3 operating modes: variable flow (VAV), constant flow (CAV), constant pressure (COP).
  • Communicating Modbus RTU on RS485 port or Modbus TCP/IP, BACnet IP or MSTP.
  • ETD2 remote touch control.
  • KSDE CMI insulated mixing box.

Description :
  • Classification according to EN 1886: D1/L2/F9/T2/TB2 (TUV tests)
Construction :
  • In-line construction, connection by rectangular tapping.
  • Interior and exterior made of alloy steel (Zn-Al-Mg) ZM310, corrosion resistance C5.
  • Self-supporting structure in 50 mm double-skin panels.
  • Insulation with mineral rock wool, thickness 50 mm, density 40 kg/m3,
    • Thermal conductivity 0.037 W/(mk) (20/80°C).
    • Fire classification A1 according to standard EN 13 501.1.
  • Metallic freewheel type reaction fan (incombustible A1) associated with an electronically commutated ECM motor.
    Switch mounted/wired.
  • Frame made of ZM310 alloy steel, 3 mm thick.
  • Access doors to the main components mounted on hinges, opening by 1/4 turn screw.
  • Motorized sealed register inside the CTA :
    • Dual function: antifreeze protection of water batteries and response to article CH 38 of the fire regulations in ER

Motorization
  • Three-phase motor with integrated electronic protection:
    • KSDE 55 / 75 / 160: Tri 400 V, 50/60 Hz, IP54, class B.
    • KSDE 40 / 95 / 120 / 200: Tri 400 V, 50/60 Hz, IP55, class F.

Filtration
  • Filters supplied as standard: FIFI M5 ePM10 50 mini-pleat filters%.
  • Additional filters available as an option:
    • HPE FIFI F7 ePM1 55 Mini-Pleat Filters%.
    • HPE FIFI F9 ePM1 80 Minipleat Filters%.
  • Additional options in sizes 160 and 200:
    • FIFI F7 ePM1 60 bag filters%.
    • FIFI F7 ePM1 55 Dihedral Filters%.
    • FIFI F9 ePM1 85 bag filters%.
    • FIFI F9 ePM1 80 dihedral filters%.

Regulation
  • CORRIGO regulation mounted/wired, integrated into the unit in a dedicated compartment, with remote touch control, allowing 3 operating modes:
FLOW RATE SETTINGSRECOMMENDED APPLICATIONS
VAV MODE - VARIABLE FLOW
Fan speed variation
- Flow rate depending on a 0-10 V signal from the extraction, the remote control, an external probe (CO2, temperature, humidity, etc.) or a remote control (M/A + variation).- Compensation, controlled by a kitchen extraction,
- Single-zone installations, requiring adaptation of ventilation depending on occupancy.
CAV MODE - CONSTANT FLOW
Fan speed set to a specific flow rate
- Manual entry (m3/h) of 3 flow rate settings type 0-PV-GV-BOOST. Manual operation or on time slot.
- Visualization of values on the display, manual switching, by clock or external contact.
- Installations requiring control of one or more specific flow rates.
COP MODE - CONSTANT PRESSURE
Automatic fan speed variation to maintain constant pressure
- Constant pressure value measured by an external probe (option) located in the blowing duct network.- Multi-zone installations, associated with modulation of terminal flow rates.

KSDE delivered in CAV mode, without accessories.


EI / EIX / EIR electric batteries
  • 304L stainless steel resistors.
  • Safety thermostats: one thermostat with automatic reset, one thermostat with manual reset.
  • Pulse train control.
  • Post-ventilation.
  • Load shedding control possible depending on battery characteristics: total load shedding for 1-stage batteries and partial or total load shedding for 2-stage batteries.
  • The 400V three-phase power supply of the electric battery is separate from the main power supply, regulation and fan(s).

Hot water/reversible batteries EC / ECF / ER / ERC / EIR
  • 2, 3, 4, 6 or 8 row battery depending on the model, with copper tubes, aluminum fins, galvanized steel frame; threaded connection tubes.
  • Right or left connection in the direction of air flow.
  • Frost protection by contact probe.
  • Battery(ies) mounted on slide accessible via side hatch.
  • Stainless steel condensate tray and droplet separator for reversible versions.
  • Motorized 3-way valve (24V) proportional by signal (0-10V), optional, not mounted.

EX direct expansion battery / EIX electric direct expansion battery: sizes 40 to 120
  • Reversible battery 1 or 2 circuits on 4 rows for operation as a condenser or evaporator; copper tubes and collectors, aluminum fins, galvanized steel frame. Stainless steel condensate recovery tray and droplet separator.
  • Provide a CTA kit with the direct expansion unit (not supplied) equipped with its own probes and temperature regulation system. In the case of a direct expansion battery, the CORRIGO regulator manages, apart from the preheating temperature on EIX models, only the ventilation and does not manage the temperature regulation at the DX battery outlet.
  • EIX version: preheating of the direct expansion battery with electric battery. Control, set point and post-ventilation of the preheating battery provided by the Corrigo.
  • COP mode regulation not compatible with a direct expansion battery.

CMI Mixing Box
  • 1 or 2-way mixing module equipped with motorized register(s) and temperature probe(s).
  • Identical construction to KSDE with interior and exterior versions.
  • CTA suction assembly.
  • The 1-way module allows you to change the orientation of the fresh air intake.
  • The 2-way module allows mixing of fresh air and indoor air depending on the CO2 level or temperature or for recycling.
  • The control of the motorized registers is ensured by the KSDE regulation.
  • Possible choices of positions for fresh air and return air intakes

Air treatment selection
KSDE ECOWATT

Interior model 40 to 120
KSDE-ECOWATT-INT-dim.jpg

Interior model 160 - 200
KSDR-ECOWATT-160-200-dim.jpg

Outdoor model 40 to 120

KSDE-ECOWATT-EXT-dim.jpg


Outdoor model 160 - 200

KSDR-ECOWATT-160-200-ext-dim.jpg


SizesABCDEFG (except EI)G (EI)HIIKMOPQ
40177471654654685015512054574574160570322955950585
5518009918206209251551205484065016080333512321026630
75186498882083011621551205484085016080334712321264664
952000130010948301162155120541140850160110943515411282695
120235013001094110014601551205411401150160110940015411575750
1602800161012101160148514010065124012161601380-18201615750
2002800195015151160148514010065154512161601688-21201625750


SizesKSDE weight (kg)
Interior model - Without roofExterior Model - With roof
EIEIX / EIFECEREXECFERCERREIEIX / EIFECEREXECFERCERR
40285307249264256271279286307329271286278293301308
55328356295314304323333342355383322341331350360369
75392431367391378406419430420459395419406434447458
95456504436479450484513527491539471514485519548562
120516579505563524568607626557620546604565609648667
160671732655772687732817844719780703820735780865892
20088195287610179079631073110093810219331074964102011301157

Close Open Detailed specifications

Text catalog pages (CT)

Catalog Pages - Other

Close Open Public tariff price

Close Open Installation instructions

Installation instructions (NT)

Installation instructions (NT) Other languages

Close Open Fire / Smoke extraction certificates

Fire classification report (PVFEU)

Close Open Electrical / ATEX Certificates

Electrical CE Declarations (DCCE)

Close Open Prescription assistance

Specification text (TP)

Close Open Commercial documents

X