CAD HR BASIC V

Old ranges

Counter current - Reaction - ECM < 5600 m3/h

CAD HR BASIC V View larger

CAD HR BASIC V

Old ranges


Counter current - Reaction - ECM < 5600 m3/h

Conforme ErP 2018 - UVNR - Moteurs EC variables ErP 2018 compliant - UVNR
Variable EC motors
Filters
Supplied as standard: Blowing fresh air: FIFI F7 ePM1 55 mini-pleat filters%.
Resumption
stale air: FIFI M5 ePM10 50 pleated filters%.

Available as an option: Blowing fresh air: FIGR G4 Coarse 70 pleated filter% + FIFI F7 ePM1 55 minifold filter%,
FIFI M5 ePM10 50 pleated filter% + FIFI F9 ePM1 80 minipleat filter%.
Resumption stale air: FIFI F7 ePM1 55 mini-pleat filter%
Échangeur à contre-courant Moteur ECM By-pass Batterie chaude ou froide
Débit ou pression régulés GTC modbus / BACnet Régulation Plug and Play OPTAIR® CTA
Logo-EUROVENT.jpg
Air-to-air plate heat exchanger produced by RECUTECH, a company participating in the Eurovent program. Certification for AAHE.





  • Double skin insulation 36 mm
  • With or without integrated battery
  • Freewheel jet fan
  • Low consumption ECM motor
  • Thermal efficiency up to 90%

Application

Air introduction and extraction with energy recovery.
Indoor or outdoor use with rain cover.

  • Description

  • Dimensions

  • Documentation

  • Public Price

  • Software

  • References

7 sizes: 07 (700 m3 /h) / 11 (1,100 m3 /h) / 16 (1,600 m3 /h) / 25 (2,500 m3 /h) / 32 (3,200 m3 /h) / 45 (4,500 m3 /h) / 56 (5,600 m3 /h)
6 models according to types of integrated batteries:

Electric post-heating Reversible water Electric antifreeze
E
ED
EI
EDI
ER
EDR

Vertical construction with in-line duct connection.
Right (R) or left (L) servitude in the direction of the blown air.
New integrated EVCO regulation specific to VIM . Communicating Modbus RTU on RS485 port or Modbus TCP/IP, BACnet IP, remote EPJcolor touch control.
Bypass 100% modulating.

Construction
  • Self-supporting structure in extruded aluminum profile, rounded corners.
  • 45 mm double skin panel in alloy steel (Zn - Al - Mg) ZM310 for environments with corrosiveness C4 medium durability or C5 low durability, insulation by injected polyurethane foam (42 kg/m3 – 0.0246W/mk) fire classification B-S2, d0 (M1).
  • Vertical construction with in-line connection by circular tappings equipped with sealing joints.
  • Galvanized steel frame for floor mounting.
  • Possibility of adapting the position of certain tappings on site.
  • Access to filters, exchanger, battery and fan from the side.
  • Ø1/2˝ purge for condensate drainage.

Interchange
  • High efficiency counter-flow aluminum plate heat exchanger. Thermal efficiency up to 90%.
  • Motorized bypass 100%, integrated into the unit on the fresh air network.
  • 230V single-phase 3-point servomotor controlled proportionally by adjusting the running time.

Motorization
  • Freewheel type fan with metal reaction (incombustible A1).
  • High efficiency ECM motor, 400V 50/60Hz on size 45, 230V 50/60Hz on other sizes.
  • Control by 0…10V signal.
  • CAD HR BASIC E/EI/EC 06: IP44 Class B,
  • CAD HR BASIC E/EI/EC 11 - 16 - 25 - 32 - 56: IP54 Class B.
  • CAD HR BASIC E/EI/EC 45: IP54 Class F.
  • Electronic thermal protection.

Filtration

Filters supplied as standard:

  • Fresh air blowing: FIFI F7 ePM1 55 mini-pleat filters%.
  • Stale air intake: FIFI M5 ePM10 50 pleated filters%.

Optional filters available:

  • Blowing fresh air:
    • FIGR G4 Coarse 70 pleated filter% + FIFI F7 ePM1 55 minifold filter%,
    • FIFI M5 ePM10 50 pleated filter% + FIFI F9 ePM1 80 minipleat filter%.
  • Stale air intake: FIFI F7 ePM1 55 mini-pleat filter%

EI post-heating electric battery
  • Connected to the regulation, it allows the temperature of the blown air to be regulated.
  • Equipped with safety thermostat with automatic reset (set point 55°C) and manual reset (set point 70°C).

ED antifreeze electric battery
  • Placed on the fresh air before the exchanger, prevents the risk of freezing on the exchanger.
  • Assembled, wired and controlled by the regulator.
  • Safety thermostat with automatic reset (set point 55°C) and manual reset (set point 70°C).

ER2R and ER3R reversible hot/cold water battery
  • 2-row (ER2R) or 3-row ER3R water battery.
  • Composed of copper tubes with aluminum fins on a galvanized steel frame.
  • Copper collector.
  • Threaded connecting tube.
  • Condensate outlet to be connected to a siphon when used in cold conditions.
  • 230V/24V 10VA power supply for power supply of 2V or 3V valve, CO2 probe, fresh air register servomotor...

Air treatment selection

See catalog pages CT-CAD-HR-BASIC-V-230809

Close Open Detailed specifications

Text catalog pages (CT)

Catalog Pages - Other

Close Open Installation instructions

Installation instructions (NT)

Installation instructions (NT) - Old version

Close Open Performance / Environment Certificates

ErP regulatory sheet (FERP)

Eurovent certificate (CEUR)

Close Open Electrical / ATEX Certificates

Electrical CE Declarations (DCCE)

Close Open Prescription assistance

Specification text (TP)

OPTAIR CTA
Download the new OPTAIR CTA version (No automatic update from the previous version) Media locked

For any questions, please send an email to optair@vim.fr

AIR TREATMENT
OPTAIR-CTA.png Selection of single or double flow CTAs
  • Sizing and quotation in price list
  • Calculation of exchanger efficiency
  • Engine consumption
  • Selection of accessories
  • Battery characteristics
  • Acoustic characteristics

UTBS ECOWATT
UTBS ECOWATT PRO-REG
KSCR ECOWATT
KSDR ECOWATT
CAD O INTEGRAL
CAD HR MINI
CAD HR MINI TOP
CAD HR BASIC H
CAD HR BASIC V
CAD HR BASIC TOP
CAD HR DUO H
CAD HR DUO V
CAD HR SLIM
CAD HR FIRST H
CAD HR FIRST V
CAD HR BASIC XL

ESPACE PORTE DE NIORT - SAINT JEAN D'ANGELY

Close Open ESPACE PORTE DE NIORT - SAINT JEAN D'ANGELY

Hotel residences

17 - Charente-Maritime


Installed products:


LE GRAND REFECTOIRE DE L'HOTEL DIEU

Close Open LE GRAND REFECTOIRE DE L'HOTEL DIEU

Independent commercial catering

69 - Rhône

X